Cabinet type gas automatic fire extinguishing device
The Cabinet type gas automatic fire extinguishing device is used to extinguish fire
- Description
- Inquiry
Product Name: Cabinet type gas automatic fire extinguishing device
1.Product parameter
| nominal working pressure | 2.5MPa | |||
| Maximum working pressure | 4.2MPa | |||
| Gas Injection time | ≤10(s) | |||
| Filling density | ≤1150(Kg/m3 ) | |||
| bottle volume | 70 | 90 | 120 | 150 |
| working temperature | 0℃~50℃ | |||
| Nominal working pressure of nozzle | 1MPa | |||
| Protection radius of single nozzle | ≤7.5(m) | |||
| Protection Height of Nozzle | 0.3—6.5(m) | |||
| Fire extinguishing technology | Total flooding | |||
| staring power | 24V,≤1.6A | |||
| Operation Pressure of Safety Release Device | 5.6±0.28MPa | |||
| size(mm) | 500×500×1500 | |||
2.Features
■There is no need to install a pipe network, nor to set up a dedicated bottle group room, and the cabinet fire extinguishing
device is set in the protection area.
■The design calculation and scheme are simple.
■Suitable for new and old projects.
■The installation is simple and fast, the construction period is short, and the installation time for a single unit is about two
hours.
■Suitable for projects with a protected area less than 500m2 or a volume less than 1600m3.
■When a building has less than four protection zones, the cost performance is higher.
■The appearance is beautiful, high-end, and the appearance patent has been obtained.
■Adopt horizontal pressure difference type double-sealed structure container valve, which has reliable sealing and safety
performance.